Model KGN1
smoke sensor, mine-used Intrinsic Safety sensor, is
suitable for monitoring the fire event out of mechanical
friction, cable heating and coal layer in the coal mine
underground. It can be installed in the belt
transportation laneway, the electromechanical chamber, the
goaf and the working face.
Model KGN1 can be connected
with the power cuttingoff device and the acousto-opticl
alarm device to realize the alarm and the power cuttingoff
control. It can also be equipped with the production and
safety monitoring and control system. |
 |
|
|
| Power
Supply: |
Intrinsic
Safety power supply 12.5
18V |
| Operating
Current: |
60mA |
Detection
Sensitivity:
Level I (smoke concentration 0.1mg/m ,
response time 15s) (KGN1-1)
Level II (smoke concentration 0.1mg/m ,
response time 30s) (KGN1-2)
Level III (smoke concentration 0.1mg/m ,
response time 60s) (KGN1-3) |
Output
Signals:
On-off current signal 0/5mA (KGN1-A)
Normal-open contact of the relay 24V/2A
(KGN1-B)
Normal-close contact of the relay 24V/2A
(KGN1-C) |
Indication
and alarming of power supply:
Red LED power indicator, flashes when
alarmaing, frequency 1Hz |
| Explosion-proof
Type: |
ExibI |
| Overall
Dimensions: |
150mm*150mm*155mm |
| Weight: |
1kg |
|
|
|
|
|